L-9052AB
InLog L-9052 AB Digital Ethernet 8-ch Input Dry/Wet Contact and 8-ch Output mod
L-9052AB
- Support Modbus/TCP,TCP/IP,UDP,ICMP,ARP
- Ethernet 10/100 Based-T Communication
- Support 8 isolated digital output with Open Drain.
- Provide 3A/per output channel.
- Provide Pulsed/delay Output Mode
- Support 8 Isolated digital Input Channels
- Support Dry/Wet Contact Inputs
- Fully Photo-Isolation 3750Vrms
Details
L-9000 Analogue and DIO Series is based on the popular Ethernet networking standards used today in most business environments. Userscan easily add L-9000 I/O modules to existing Ethernet networks or use L-9000 modules in new Ethernet-enabledManufacturing networks. L-9000 module features a 10/100 Mbps Ethernet chip and supports industrial popular Modus/TCPprotocol over TCP/IP for data connection. L-9000 also supports UDP protocol over Ethernet networking. With UDP/IP, L-9000I/O modules can actively send I/O data stream to 8 Ethernet nodes. Through Ethernet networking HMI/SCADA system andcontroller can access or gather real-time data from L-9000 Ethernet enabled DA&C modules. And, these real-time data can beintegrated with business system to create valuable, competitive business information immediately.
Enhancing from traditional I/O modules, L-9000 I/O modules have pre-built intelligent mathematic functions toempower the system capacity. The Digital Input modules provide Counter, Totalizer functions; the Digital Outputmodules provide pulse output, delay output functions; the Analog Input modules provide the Max./Min./Average datacalculation; the Analog Output modules provide the PID loop control function.
L-9000 mixed I/O module design concept provides the most cost-effective I/O usage for application system. Themost common used I/O type for single function unit are collected in ONE module. This design concept not onlysave I/O usage and spare modules cost but also speed up I/O relative operations. For small DA&C system orstandalone control unit in a middle or large scale, L-9000 mixed I/O design can easily fit application needs by oneor two modules only. With additional embedded control modules, L-9000 can easily create a localized, lesscomplex, and more distributed I/O architecture.L-9000 modules support the popular industrial standard, Modbus/TCP protocol, to connect with Ethernet Controlleror HMI/SCADA software built with Modbus/TCP driver. Inlog also provides OPC server for Modbus/TCP to integrateL-9000 I/O real-time data value with OPC client enabled software. Users don’t need to take care of special driver’sdevelopment.
Downloads
System Integration
Please ask about how we can configure your solution
Global Operations
We deliver and support products via offices globally
Full Warranty
Industry leading warranties on all solutions as standard
Technical Support
Experienced engineers are on hand to support your project
Can't Find What You Want?
Specification
Interface | |
Communication | 10/100 Based-T Ethernet |
Protocol | TCP, TCP/IP, UDP, ICMP and ARP |
Command Protocol | ASCII Format, Modus/TCP |
Digital Input | |
Channel | 8 Channels |
Input Level | Logic Level Status can be inversed via ASCII/Modbus command |
Input Type | Isolated single ended with common source (Dry/Wet Contact) |
Dry Contact |
Logic Level 1 (active): Close to GND Logic Level 0 (inactive): Open |
Counter Input |
500Hz counter input (32-bit + 1-bit overflow) |
Optical Isolation Voltage |
3750 Vrms |
Digital Output | |
Channel | 8 Channels |
Digital Output | isolated open collector (NPN) |
Output logical level | Logic level status can be inversed via ASCII/Modbus command |
Output Load Voltage | +5V ~ +30Vdc |
Max Load Current | 3 A/per channel (total 8 output channels maximum 8A) |
Pulse Output | Each Channel supports 1KHz pulse output |
Optical Isolation | 3750 Vrms |
Display | |
Status Indicator | LED indicator |
Common | |
Power Requirement | +10 to +30VDC |
Power Consumption | 1.8 W (Typical) |
Case | ABS + PC with captive mounting hardware |
Accessories | DIN-rail Mounting Adapter, Panel Mounting Bracket |
Delivery Information
Orders dispatched from Assured Systems USA will be delivered using FedEx.
Payment Methods & Options
Accepted payment methods for US customers include bank transfer, VISA or Mastercard in USD.
InLog: Warranty and Service Information
Assured Systems offers a 2 year warranty on all InLog products supplied in the EMEA, with extended warranty options available upon request.
Related Products
You may also like...