L-9015

InLog L-9015 Analogue Ethernet-based 7-ch RTD Input Module 16 Bit

L-9015

  • Ethernet 10/100 Based-T communication
  • Support protocol Modbus/TCP,TCP/IP,UDP,ICMP,ARP
  • Burn-out auto detection
  • Support PT100,PT1000,NI604,NI1000 RTD types
  • Support isolated input channels
  • Built-in TVS/ESD protection
  • Wide supply voltages (10~30V)
  • Fully photo-isolation 3750Vrms
-
+

Details

L-9000 Analogue and DIO Series is based on the popular Ethernet networking standards used today in most business environments. Userscan easily add L-9000 I/O modules to existing Ethernet networks or use L-9000 modules in new Ethernet-enabledManufacturing networks. L-9000 module features a 10/100 Mbps Ethernet chip and supports industrial popular Modus/TCPprotocol over TCP/IP for data connection. L-9000 also supports UDP protocol over Ethernet networking. With UDP/IP, L-9000I/O modules can actively send I/O data stream to 8 Ethernet nodes. Through Ethernet networking HMI/SCADA system andcontroller can access or gather real-time data from L-9000 Ethernet enabled DA&C modules. And, these real-time data can beintegrated with business system to create valuable, competitive business information immediately.

Enhancing from traditional I/O modules, L-9000 I/O modules have pre-built intelligent mathematic functions toempower the system capacity. The Digital Input modules provide Counter, Totalizer functions; the Digital Outputmodules provide pulse output, delay output functions; the Analog Input modules provide the Max./Min./Average datacalculation; the Analog Output modules provide the PID loop control function.

L-9000 mixed I/O module design concept provides the most cost-effective I/O usage for application system. Themost common used I/O type for single function unit are collected in ONE module. This design concept not onlysave I/O usage and spare modules cost but also speed up I/O relative operations. For small DA&C system orstandalone control unit in a middle or large scale, L-9000 mixed I/O design can easily fit application needs by oneor two modules only. With additional embedded control modules, L-9000 can easily create a localized, lesscomplex, and more distributed I/O architecture.L-9000 modules support the popular industrial standard, Modbus/TCP protocol, to connect with Ethernet Controlleror HMI/SCADA software built with Modbus/TCP driver. Inlog also provides OPC server for Modbus/TCP to integrateL-9000 I/O real-time data value with OPC client enabled software. Users don’t need to take care of special driver’sdevelopment.Based on the Modbus/TCP standard, the L-9000 firmware is a built-in Modbus/TCP server. Therefore, Inlogprovides the necessary DLL drivers, and Windows Utility for users for client data for the L-9000. Users canconfigure this DA&C system via Windows Utility; integrate with HMI software package via Modbus/TCP driver orModbus/TCP OPC Server. Even more, you can use the DLL driver and ActiveX to develop your own applications.

Downloads

System Integration

Please ask about how we can configure your solution

Global Operations

We deliver and support products via offices globally

Full Warranty

Industry leading warranties on all solutions as standard

Technical Support

Experienced engineers are on hand to support your project

Can't Find What You Want?

Specification

Interface  
Communication 10/100 Based-T Ethernet
Protocol Modus/TCP, TCP/IP, UDP, ICMP and ARP
LED Indication LED For Power and Ethernet Link Status
Analogue Input  
Input Channels 7 Differential
Input Impedance

>10MΩ

Effective Resolution 16-bit
Input Type PT100, PT1000, NI RTD
Input Range

PT100 -50~150°C, 0~100°C, 0~200°C, 0~400°C, -200~200°C

PT1000 -40~160°C, NI518 -80~100°C

RTD Standard

IEC RTD 100Ω (a=0.0385)

JIS RTD 100Ω (a=0.0392)

Isolation Fully Photo-Isolation 3750Vrms
Sampling Rate 10 Samples/Sec (16 Bit)
Accuracy

±0.1% Or Better

Zero Drift ±0.5uV/ °C
Span Drift ±20ppm/ °C
CMRR 90dB Min. @50/60Hz
Burn-Out Wire Burn-Out Audio Detection
Over Voltage Protection +/- 35V
Power Requirement  
 Consumption 2.2W
Power Input 10~30VDC (Unregulated)

Delivery Information

Orders dispatched from Assured Systems USA will be delivered using FedEx.

Payment Methods & Options

Accepted payment methods for US customers include bank transfer, VISA or Mastercard in USD.

InLog: Warranty and Service Information

Assured Systems offers a 2 year warranty on all InLog products supplied in the EMEA, with extended warranty options available upon request.

Related Products

You may also like...

ADAM-4017+

Advantech ADAM-4017+ 8-ch Analog Input Module with Modbus

ADAM-4013

Advantech ADAM-4013 1-ch RTD Input Module

ADAM-4068

Advantech ADAM-4068 8-ch Relay Output Module with Modbus

ADAM-4520

Advantech ADAM-4520 Isolated RS-232 to RS-422/485 Converter