L-8015

InLog L-8015 Analogue 6-ch Isolated RTD Input Module 16-Bit

L-8015

  • Support PT100,PT1000,Balco 500,NI604,NI1000 RTD Types
  • Protocol Modbus RTU, ASCII Command
  • Support Isolated Input Channels
  • Fully Photo-Isolation 3750Vrms
  • Wide Supply Voltages (10~30V)
  • Built-In TVS/ESD Protection
  • Burn-Out Auto Detection
-
+

Details

The L-8000 DIO modules is a set of intelligent sensor to computer interface modules containing built-in microprocessor. They provide data comparison and digital communication functions. Some modules provide digital I/O lines for controlling relays and TTL devices.

The L-8000 series are fully compatible to Advantech ADAM-4000 series, ADlin NμDAM-6000 series and ICP I-7000 series.L modules can connect to and communicate with all computers and terminals.  They use RS-485 transmission standards, and communicate with ASCII format protocol(default) or Modbus-RTU protocol(for firmware version D02.01 and later), which means that L modules can be programmed in virtually any high-level language.

Up to 256 L modules may be connected to an RS-485 multi-drop network by using the L RS-485 repeater, extending the maximum communication distance to 4,000 ft.

Downloads

System Integration

Please ask about how we can configure your solution

Global Operations

We deliver and support products via offices globally

Full Warranty

Industry leading warranties on all solutions as standard

Technical Support

Experienced engineers are on hand to support your project

Can't Find What You Want?

Specification

Interface  
Communication RS485
Protocol MODBUS RTU and ASCII Command
Baute Rate (bps) 1200, 2400, 4800, 9600, 19.2K,38.4K, 115.2K
LED Indication LED for Power and link status
Isolation Voltage 3000VDC
Analogue Input  
Effective Resolution 16-Bit
Input Channels 6 channel RTD input (2-wires,3-wires, 4-wires)
Input Range PT100, PT10000, Balco 500, NI RTD
Isolation Voltage 2000V
Sampling Rate 12 Samples / Second
Input Impedance 20M ohm
Accuracy ±0.05% or better
Zero Drift ±0.5uV/ °C
Span Drift ±20uV/ °C
CMRR 50/60 Hz: 92 dB
Burn-Out Wire burn-out auto detection
Over Voltage Protection ±60V
Power Requirement  
Power Consumption 0.8W/Typical
Operating Temperature +10 ~ +30 VDC
Humidity  5 ~ 95% RH, non-condensing

Delivery Information

Orders dispatched from Assured Systems USA will be delivered using FedEx.

Payment Methods & Options

Accepted payment methods for US customers include bank transfer, VISA or Mastercard in USD.

Related Products

You may also like...

104-AI12-8

PC/104 Analog Input Board

104-AIO12-8

PC/104 Analog I/O Board

104-AO12-4

PC/104 Analog Output Board

USB-104-IHUB

Industrial 4 Port Isolated USB Hub